Uei-test-instruments SMART BELL Bedienungsanleitung Seite 8

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 16
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 7
atmoSPheriC gaS fired BurNerS
• Oxygen .............................................................................6.8to7.9%O2
• Stack Temperature .........................................................325to500°F
• Draft (WaterColumnInches) ..........................................-.02to-.04wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
gaS fired Power BurNerS
• Oxygen .............................................................................8.5to10.2%O2
• Stack Temperature .........................................................275to500°F
• Stack Draft (WaterColumnInches) ...............................-.02to-.04wc”
• Overfire Draft (WaterColumnInches) ..........................-.02wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
oil fired BurNerS (#2 oil fuel)
• Oxygen .............................................................................10to12%O2
• Stack Temperature .........................................................325to600°F
• Stack Draft (WaterColumnInches) ...............................-.04to-.06wc”
• Overfire Draft (WaterColumnInches) ..........................-.02wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
• Smoke ..............................................................................0
(ormanufacturer’srecommendation)
PoSitive overfire gaS & oil
• Oxygen .............................................................................7to13%O2
• Stack Draft (WaterColumnInches) ...............................-.02to-.04wc”
• Overfire Draft (WaterColumnInches) ..........................+0.4to+0.6wc”
• Carbon Monoxide(partspermillion) ............................<100ppm
NOTE:Followmanufactureguidelinesforthespecificequipmentbeingserviced.
uei reCommeNdS the Co91 to teSt Co levelS
WHAT RESULTS ARE GENERALLY ACCEPTABLE
6
Seitenansicht 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Kommentare zu diesen Handbüchern

Keine Kommentare